Condensate Acidic Neutralizing Tubes
Suggested Specifications
  1. The contractor shall supply and install fireside condensate neutralizing tubes for each boiler condensate drain and all flue pipe condensate drains.
  2. The condensate tubes shall be designed to raise the PH level 10–1,000 times more towards the neutral point of the PH being discharged by the boiler or furnace.
  3. The neutralizer tube or tubes shall be Model ( ), as manufactured by JMM Boiler Works.
  4. The installing contractor shall supply all boilers/furnaces and vent condensate drains with “P-traps” and unions before the neutralizing tubes.
  5. All piping shall be PVC and supplied/installed by the contractor. Plastic tubing is an acceptable alternative when used with barbed fittings and hose clamps. All PVC joints shall be glued in place and all barbed fittings shall be secured with tie wraps.
  6. The boiler and flue condensate drains shall not be combined into one neutralizer. All piping shall be per manufacturer’s piping diagrams and directions. All neutralizing tubes shall be secured to the floor or wall so as not to be exposed to damage or within a normal walkway. The contactor shall fill all “P-traps” and neutralizing tubes with tap water before the firing of any boiler.
  7. The contractor shall inform the owner of any maintenance or scheduled recharge of the tube’s limestone aggregate as described in the manufacturer’s I and O manual.

 


Figure 1 JM-series Condensate Neutralizing Tubes - features and dimensions

JM-series condensate neutralizing tubes features and dimensions.

 

FEATURES
RATINGS & DIMENSIONS (in inches)
Item
Description
Model
MBH
GPH
A
B
C
D
E
F
1
PVC tubing filled with ½" and ¾" aggregate calcium carbonate
JM-2
200
2
15
3 78
N/A
2
Channel strut mounts
JM-6
600
6
14¼
4
6
10¾
3
Galvanized strut clamps, bolts and nuts
JM-10
1,000
10
19
4
6
16 18
4
Condensate outlet hose barb fitting
JM-2 to -30: ¾" hose barb x ½" NPT
JM-20
2,000
20
19½
5
6
16 18
3 18
5
Condensate inlet hose barb fitting
JM-40 to -50: 1" hose barb x ¾" NPT
JM-30
3,000
30
24½
5
6
21
3 18
6
Plugged - alternate location for condensate inlet hose barb fitting
JM-40
4,000
40
22½
7 316
8
19
 
JM-50
5,000
50
28½
7 316
8
24